Evaluation Report CCMC 13568-R
DMX Drain 5M (Drainage)
- MASTERFORMAT:
- 33 46 23.01
- Evaluation issued:
- 2013-05-09
- Re-evaluated:
- Never
- Revised:
- Never
- Re-evaluation due:
- 2016-05-09
- Re-evaluation in progress
- No
1. Opinion
It is the opinion of the Canadian Construction Materials Centre (CCMC) that “DMX Drain 5M (Drainage)”, when used as a foundation wall drainage material in accordance with the conditions and limitations stated in Section 3 of this Report, complies with the Ontario Building Code 2006:
- Clause 1.2.1.1.(1)(a), Division A, using the following acceptable solutions from Division B:
- Clause 9.14.2.1.(2)(b) Foundation Wall Drainage
This opinion is based on CCMC's evaluation of the technical evidence in Section 4 provided by the Report Holder.
2. Description
The product consists of a dimpled, high-density polyethylene membrane (DMX AG CCMC #13182-R) laminated to a geotextile filter fabric. The membrane is installed on the foundation wall with the raised dimples facing away from the wall.
The product is available in rolled sheets that are 0.6 mm thick, 20 m long and up to 2.4 m wide. When two sheets are joined side-by side, they must be overlapped by 150 to 300 mm with their dimples meshing; when two sheets are joined top-to-bottom (horizontally), they must be overlapped by 150 mm (minimum).
A range of accessories, such as special trim strips, plugs and nails, is available to ensure correct application of the product.

- dimpled high-density polyethylene sheet
- geotextile filter fabric

- drainage tile
- membrane
- concrete foundation
- minimum 150 mm overlap (refer to manufacturer's installation guide for details)
- caulking and fasteners at top edge and all laps
3. Conditions and Limitations
CCMC's compliance opinion in Section 1 is bound by the “DMX Drain 5M (Drainage)” being used in accordance with the conditions and limitations set out below.
- The product has been evaluated for use against cast-in-place and concrete block foundations only.
- The product is only one component of the total foundation drainage system, which must be installed in accordance with Article 9.14.2.1. of the OBC 2006.
- The product can only be installed with the dimples facing away from the wall and must be protected from exposure to ultraviolet radiation from the sun within 30 days of its installation.
- The product is evaluated for use in depths up to 3.7 m below grade. Application depths greater than 3.7 m are considered to be outside the scope of this Report.
- The product is suitable for use in pervious and semi-pervious soil conditions that allow for some drainage through the soil. Such soils include very fine sand, organic and inorganic silts, mixtures of sand, silt and clay, glacial till, and stratified clay deposits that have a soil grain size defined by D10 > 0.002 mm, where D10 is the sieve size that permits 10% by weight of the soil to pass through it in a sieve analysis test.
- The product is not to be used in practically impervious soil conditions (e.g. homogeneous clays below zone of weathering) where the soil grain size is D10 < 0.002 mm.
- The product must cover the foundation wall from the top of the footing to the final grade.
- The top of the membrane must be mechanically fastened and sealed.
- All vertical joints and terminations must be mechanically fastened and sealed.
- As the drainage membrane does not have to adhere to the surface and can permanently bridge any normal joint, tie hole, fault or shrinkage crack, the wall surface does not have to be parged, cleaned, patched or sealed before hanging the membrane.
- The product has also been evaluated for use as a foundation wall dampproofing material. For details, see CCMC # 13571-R.
- The product label and/or packaging must be clearly identified with the following:
- manufacturer’s name or logo, and
- the phrase “CCMC 13568-R”.
4. Technical Evidence
The Report Holder has submitted technical documentation for CCMC’s evaluation. Testing was conducted at laboratories recognized by CCMC. The corresponding technical evidence for this product is summarized below.
4.1 General
| Properties | Requirements | Results | ||
|---|---|---|---|---|
| Compressive strenghth (kN/m2)Table 4.1.1 footnote 1 | 100 | 419 | ||
| Impact load | Min. 12 of 15 shall pass a rating of 3 | 30 of 30 | ||
| Static puncturing | Min. 5 of 6 shall pass a rating of 3 | 12 of 12 | ||
| Cold bending | No visible cracking | No visible cracking | ||
| Tensile strength | At yield (kN/m) | Min. 8 | MD 13.7Table 4.1.1 footnote 2 | |
| Elongation at break (%) | Min. 25 | MD 52Table 4.1.1 footnote 2 | ||
| Tensile strength after water immersion | At yield (%) | Min. 80% of original | MD 123Table 4.1.1 footnote 2 | |
| Elongation at break (%) | Min. 70% of original | MD 149Table 4.1.1 footnote 2 | ||
| Heat aging | Dimensional change (%) | ± 1 | Width –0.2 | |
| Length –1.3Table 4.1.1 footnote 3 | ||||
| Weight change (%) | Max. 0.10 | –0.3 | ||
| Tensile strength (%) | Min. 80% of original | MD 99Table 4.1.1 footnote 2 | ||
| Elongation (%) | Min. 70% of original | MD 74Table 4.1.1 footnote 2 | ||
| Chemical attack exposure | Ammonium chloride | Tensile strength (%) | Min. 80% of original | MD 95Table 4.1.1 footnote 2 |
| Elongation (%) | Min. 70% of original | MD 111Table 4.1.1 footnote 2 | ||
| Sodium sulfate | Tensile strength (%) | Min. 80% of original | MD 97Table 4.1.1 footnote 2 | |
| Elongation (%) | Min. 70% of original | MD 120Table 4.1.1 footnote 2 | ||
Notes to Table 4.1.1:
- Footnote 1
-
The compressive load test was done on the dimple surface
- Footnote 2
-
MD refers to the “machine direction” of the long dimension of the polymer sheet.
- Footnote 3
-
Deemed acceptable based on an acceptable compressive strength test.
| Properties | Requirements | Results |
|---|---|---|
| Grab tensile (N) | 485 | 644 |
| Elongation (%) | 20 | 62.6 |
| Puncture resistance (N) | 180 | 251 |
| Apparent opening size (mm) | 0.3 | 0.3 |
| Water permittivity (s-1) | 0.4 | 1.2 |
| Tearing strength (N) | 220 | 333 |
| Side waterflow (mL/15 min) 1.0 gradient at 30 kPa | 500 | Pass |
Report Holder
DMX Plastics Limited
300 Walker Drive
Brampton, ON L6T 3W9
- Telephone:
- 905-458-8998
- Fax:
- 905-458-8994
Plant(s)
Brampton, ON
Disclaimer
This Report is issued by the Canadian Construction Materials Centre, a program of NRC Construction at the National Research Council of Canada. The Report must be read in the context of the entire CCMC Registry of Product Evaluations, including, without limitation, the introduction therein which sets out important information concerning the interpretation and use of CCMC Evaluation Reports.
Readers must confirm that the Report is current and has not been withdrawn or superseded by a later issue. Please refer to the CCMC web site, or contact the Canadian Construction Materials Centre, NRC Construction, National Research Council of Canada, 1200 Montreal Road, Ottawa, Ontario, K1A 0R6. Telephone (613) 993-6189. Fax (613) 952-0268.
NRC has evaluated the material, product, system or service described herein only for those characteristics stated herein. The information and opinions in this Report are directed to those who have the appropriate degree of experience to use and apply its contents. This Report is provided without representation, warranty, or guarantee of any kind, expressed, or implied, and the National Research Council of Canada (NRC) provides no endorsement for any evaluated material, product, system or service described herein. NRC accepts no responsibility whatsoever arising in any way from any and all use and reliance on the information contained in this Report. NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.