Evaluation Listing CCMC 12423-L
ACFoam®-III/Stucco-Shield® II/Rboard™
- Evaluation Issued:
- 1992-08-28
- Re-evaluated:
- 2010-12-13
- Revised:
- Never
- Re-evaluation due:
- 2013-08-28
- Re-evaluation in progress
- Yes
Preface: Masterformat 07 21 13.07, Thermal Insulation, Polyurethane and Polyisocyanurate, Boards Faced
- Preface Issued:
- 2012-05-18
Scope
These Evaluation Listings apply to closed-cell polyurethane and polyisocyanurate foam thermal insulation in the form of flat rigid boards covered on both sides with a facing material. The rigid boards are intended for use as thermal insulation in building construction. The continuous use temperature is within the range of –60°C to +93°C.
These rigid boards are not intended to be used as structural panels.
The standard referenced below provides a basis for evaluating products made with various facing materials, which has an impact on some physical characteristics. This standard covers only products in which the facing material has been bonded to the foam core in the original foam manufacturing process.
This standard does not apply to products made using fibreboard, perlite board, gypsum board, oriented strandboard, or any other rigid board, on one or both sides.
The proponent has demonstrated that the product meets the requirements of at least one of the following standards:
- CAN/ULC-S704-03, “Thermal Insulation, Polyurethane and Polyisocyanurate, Boards, Faced”
- CAN/ULC-S704-11, “Thermal Insulation, Polyurethane and Polyisocyanurate, Boards, Faced”
Products manufactured to this standard are classified as Type 1, 2 or 3 on the basis of their physical properties and Class 1, 2 or 3 on the basis of water vapour permeability. Typically, Type 1 products are used in wall applications, whereas Type 2 and 3 products are used in roofing applications.
Standard
| Properties | Physical Property Requirements | ||||
|---|---|---|---|---|---|
| Type 1 | Type 2 | Type 3 | |||
| Compressive strength, min., kPa | 110 | 140 | 170 | ||
| Tensile strength, min., kPa, perpendicular to the plane of the facer | 24 | 35 | 35 | ||
| Flexural strength, min., kPa | 170 | 275 | 275 | ||
| Thermal resistance (m2·°C/W): | after conditioning, min. per 25 mm thick | 0.97 | |||
| long-term thermal resistance (LTTR), min. for 50-mm-thick productTable 1 Footnote 1 | 1.90 (CAN/ULCS 704-03) | ||||
| 1.80 (CAN/ULC S704-11) | |||||
| Water vapour permeance (ng/(Pa·s·m2) for 25.4-mm-thick product): | Class 1 | ≤ 15 | |||
| Class 2 | ≥ 15 to ≤ 60 | ||||
| Class 3 | ≥ 60 | ||||
| Dimensional stability (max. % linear change): | at –29°C, ambient RH | Length | ± 2.0 | Width | ± 2.0 |
| at 80°C, ambient RH | ± 2.0 | ± 2.0 | |||
| at 70°C, 97% RH | ± 2.0 | ± 2.0 | |||
| Water absorption (max. % by volume) | 3.5 | ||||
| Dimensional tolerances (mm): | width | +4, –2 | |||
| length | +6, –4 | ||||
| thickness, ≤ 55 mm thick | +4, –1.5 | ||||
| thickness, ≥ 55 mm thick | +5, –2.5 | ||||
| flatness (mm/m) | ≤ 4 | ||||
| squareness (mm/m), ≤ 1 200 mm in length | ≤ 5 | ||||
| squareness (mm/m), ≥ 1 200 mm in length | ≤ 9 | ||||
Note to Table 1:
- Footnote 1
-
The LTTR of the material shall be reported for the purpose of energy calculations. The LTTR value shall also be reported for the 25-mm- and 75-mm-thick products.
Labelling
The product shall be marked with the following information:
As per CAN/ULC-S704-03:
- type and class;
- ULC Standard number;
- manufacturer’s name or trademark, address and telephone number;
- lot number;
- a brief generic description of the facing material used;
- the thermal resistance; and
- the product shall also be marked with a warning: “Caution: This product is combustible and shall only be used as specified by the local building code with respect to flame-spread classification and to the use of a suitable thermal barrier.”
As per CAN/ULC-S704-11:
- product name;
- ULC Standard number;
- type and class;
- manufacturer’s name or trademark, address and telephone number;
- country of manufacture;
- lot number;
- a brief generic description of the facing material used;
- LTTR value;
- quantity in surface unit;
- nominal dimension of board; and
- the product shall also be marked with a warning: “Caution: This product is combustible and shall only be used as specified by the local building code with respect to flame-spread classification and to the use of a suitable thermal barrier when required.”
National Building Code of Canada (NBC)
NBC References
CAN/ULC-S704-03 standard is referenced in Tables 5.10.1.1. and 9.23.17.2.A. and Sentence 9.25.2.2.(1) of Division B of the NBC 2010.
CAN/ULC-S704-11 standard is not referenced in the NBC 2010.
Evaluation Listing CCMC 12423-L: ACFoam®-III/Stucco-Shield® II/Rboard™
- Evaluation Issued:
- 1992-08-28
- Re-evaluated:
- 2010-12-13
- Revised:
- Never
- Re-evaluation due:
- 2013-08-28
- Re-evaluation in progress
- Yes
1. Evaluation
Conforms to CAN/ULC-S704-03, Type 2, Class 3 for products manufactured at the plants listed at the end.
2. Description
A rigid board, polyisocyanurate, thermal insulation with both sides faced with coated glass-fibre facers. “ACFoam®-III” is manufactured in thicknesses ranging from 25.4 mm to 100 mm. “Stucco-Shield® II” and “Rboard™” are manufactured in thicknesses ranging from 12.5 mm to 50.8 mm.
| Thickness (mm) | Thermal Resistance (m2·°C·W-1) |
|---|---|
| 25 | 1.044 |
| 50 | 2.089 |
| 75 | 3.174 |
| 100 | 4.264 |
The water vapour permeance is 83 ng/Pa·s·m2 at 25 mm.
3. Standard and Regulatory Information
See the Preface and the standard for explanation.
Listing Holder
Atlas Roofing Corporation
2000 River Edge Parkway, Suite 800
Atlanta, GA 30328
U.S.A.
- Telephone:
- 770-933-4478
- Fax:
- 770-952-3170
Plant(s)
Camp Hill, PA, U.S.A.
East Moline, IL, U.S.A.
Etobicoke, ON
Phoenix, AZ, U.S.A.
Northglenn, CO, U.S.A.
Disclaimer
This Listing is issued by the Canadian Construction Materials Centre, a program of NRC Construction at the National Research Council of Canada. The Listing must be read in the context of the entire CCMC Registry of Product Evaluations.
Readers must confirm that the Listing is current and has not been withdrawn or superseded by a later issue. Please refer to the CCMC web site, or contact the Canadian Construction Materials Centre, NRC Construction, National Research Council of Canada, 1200 Montreal Road, Ottawa, Ontario, K1A 0R6. Telephone (613) 993-6189. Fax (613) 952-0268.
NRC has evaluated the material, product, system or service described herein only for those characteristics stated herein. The information and opinions in this Listing are directed to those who have the appropriate degree of experience to use and apply its contents. This Listing is provided without representation, warranty, or guarantee of any kind, expressed, or implied, and the National Research Council of Canada (NRC) provides no endorsement for any evaluated material, product, system or service described herein. NRC accepts no responsibility whatsoever arising in any way from any and all use and reliance on the information contained in this Listing. NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.