Evaluation Report CCMC 12266-R
Platon Dampproofing Membrane

MASTERFORMAT:
07 11 19.01
Evaluation issued:
1991-07-26
Re-evaluated:
2013-07-19
Revised:
Never
Re-evaluation due:
2015-07-26
Re-evaluation in progress
No


1. Opinion

It is the opinion of the Canadian Construction Materials Centre (CCMC) that “Platon Dampproofing Membrane”, when used as a material for dampproofing in accordance with the conditions and limitations stated in Section 3 of this Report, complies with the National Building Code 2010:

  • Clause 1.2.1.1.(1)(b), Division A, as an alternative solution that achieves at least the minimum level of performance required by Division B in the areas defined by the objectives and functional statements attributed to the following applicable acceptable solutions:
    • Sentence 9.13.2.2.(1) Material Standards (Dampproofing)

This opinion is based on CCMC's evaluation of the technical evidence in Section 4 provided by the Report Holder.

2. Description

The product is a carbon-compounded, high-density polyethylene with a dimpled surface on one side to provide an air gap between the concrete wall and the adjacent soil.

The product features double cone dimples which are 6 mm high, spaced at about 30 mm on centre and joined by channels. The product is available in rolls that are 0.6 mm thick, 20 m long, and up to 3.05 m wide.

To ensure correct application, the manufacturer offers a complete dampproofing system with compatible and durable fasteners, sealants and accessories where needed. The configuration of the system is shown in Figure 1.

Figure 1. Installation details for the “Platon Dampproofing Membrane”
  1. speedclip (with associated spacing)
  2. continuous bead of caulking
  3. system “Platon” plugs
  4. concrete foundation
  5. foundation drainage tile
  6. water flow to tile
  7. backfill
  8. finished grade

3. Conditions and Limitations

CCMC's compliance opinion in Section 1 is bound by the “Platon Dampproofing Membrane” being used in accordance with the conditions and limitations set out below.

  • The product was evaluated for use against cast-in-place and concrete block foundations only.
  • The product must be used in locations where the foundation wall is well drained in accordance with Subsection 9.14.2, Foundation Drainage, of Division B of the NBC 2010.
  • The product must be installed in accordance with the manufacturer’s instructions and be protected from exposure to ultraviolet radiation from the sun within 30 days.
  • The product is evaluated for use in depths up to 3.7 m below grade. Application depths greater than 3.7 m are considered to be outside the scope of this Report.
  • The product must cover the foundation wall from the top of the footing to the final grade.
  • The top of the membrane and all vertical joints and terminations must be mechanically fastened and sealed to prevent soil particles from entering behind the membrane.
  • As the dampproofing membrane does not have to adhere to the surface and can permanently bridge any normal joint, tie hole, fault or shrinkage crack, the wall surface does not have to be parged, cleaned, patched or sealed before hanging the membrane.
  • The product has been evaluated for use as a foundation wall drainage material. For details see CCMC 12878-R.
  • The product label and/or packaging must be clearly identified with the following:
    • manufacturer’s name or logo; and
    • the phrase “CCMC 12266-R”.

4. Technical Evidence

The Report Holder has submitted technical documentation for CCMC’s evaluation. Testing was conducted at laboratories recognized by CCMC. The corresponding technical evidence for this product is summarized below.

4.1 General

The “Platon Dampproofing Membrane” test results are summarized in Table 4.1.1.

Table 4.1.1 Test Results for “Platon Dampproofing Membrane”
PropertyRequirementsResults
Thickness (mm) min. 0.6 in flat area 0.6
min. 0.5 in dimpled area 0.5
Weight (g/m2) min. 500 567
Impact load min. 12 of 15 15 of 15
Static puncturing (rating of 3) min. 5 of 6 6 of 6
Cold bending no visible cracking no visible cracking
Water vapour permeance (ng/Pa·s·m2) max. 37 3.0
Original sampletensile strength at yield (kN/m) min. 8 MD 12, XD 14.2
elongation at break (%) min. 25 MD 85, XD 525
Sample after water immersiontensile strength at yield (%) 80 of original MD 108, XD 109
elongation at break (%) 70 of original MD 74, XD 100
Sample after heat agingdimensional change (%) ± 1 MD −1.6Table 4.1.1 footnote 1, XD −1.4Table 4.1.1 footnote 1
weight change (%) 0.10 −0.02
tensile strength at yield (%) 80 of original MD 93, XD 104
elongation at break (%) 70 of original MD 100, XD 100
Chemical attack exposureammonium chloridetensile strength at yield (%) 80 of original MD 92, XD 98
elongation at break (%) 70 of original MD 206, XD 100
sodium sulfatetensile strength at yield (%) 80 of original MD 94, XD 99
elongation at break (%) 70 of original MD 82, XD 100
Compressive strength (kN/m2) min. 100 247Table 4.1.1 footnote 2
Notes to Table 4.1.1:
Footnote 1

Deemed acceptable based on an acceptable compressive strength test after heat aging.

Return to table 4.1.1 footnote 1 referrer

Footnote 2

The compressive load test was done on the dimpled surface.

Return to table 4.1.1 footnote 2 referrer

Report Holder

Armtec Limited
33 Centennial Road
OrangevilleON L9W 1R1

Telephone:
519-942-2643
Fax:
519-942-2850

Plant(s)

Orangeville, ON

Disclaimer

This Report is issued by the Canadian Construction Materials Centre, a program of NRC Construction at the National Research Council of Canada. The Report must be read in the context of the entire CCMC Registry of Product Evaluations, including, without limitation, the introduction therein which sets out important information concerning the interpretation and use of CCMC Evaluation Reports.

Readers must confirm that the Report is current and has not been withdrawn or superseded by a later issue. Please refer to the CCMC web site, or contact the Canadian Construction Materials Centre, NRC Construction, National Research Council of Canada, 1200 Montreal Road, Ottawa, Ontario, K1A 0R6. Telephone (613) 993-6189. Fax (613) 952-0268.

NRC has evaluated the material, product, system or service described herein only for those characteristics stated herein. The information and opinions in this Report are directed to those who have the appropriate degree of experience to use and apply its contents. This Report is provided without representation, warranty, or guarantee of any kind, expressed, or implied, and the National Research Council of Canada (NRC) provides no endorsement for any evaluated material, product, system or service described herein. NRC accepts no responsibility whatsoever arising in any way from any and all use and reliance on the information contained in this Report. NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.