Evaluation Listing CCMC 09521-L
CertainTeed Fibre Glass Building Insulation, Golden Glow Residential Fibre Glass Insulation, UFA Residential Fiber Glass Insulation, Canadian Metal Building Insulation

Evaluation Issued:
1982-02-03
Re-evaluated:
2011-01-17
Revised:
Never
Re-evaluation due:
2013-07-13
Re-evaluation in progress
Yes

Preface: Masterformat 07 21 13.19, Mineral-Fibre Thermal Insulation for Buildings

Preface Issued:
2011-06-22

Scope

These Evaluation Listings apply to mineral-fibre thermal insulation in the form of faced and unfaced batts, rolls, and boards. The proponent has demonstrated that the product meets the following standard:

  • CAN/ULC-S702-09, "Standard for Mineral Fibre Thermal Insulation for Buildings."

The standard describes five types of mineral-fibre insulation. These CCMC Evaluation Listings refer only to preformed insulation, Types 1, 2 and 3. They are defined as follows:

  • Type 1, unfaced;
  • Type 2, faced with a permeable membrane; and
  • Type 3, faced with a vapour barrier.

Standard

Table 1. Requirements for Preformed Thermal Insulation
Test/PropertyRequirements
Length -1%, +3% for batts and rolls
–3 mm, +10 mm for boards and sheets.
Width –0%, +3% for batts and rolls.
± 3 mm for boards.
Thickness Mean thickness ≥ the design thickness and none of the individual specimen thicknesses < 90% of the design thickness.
–1 mm, +3 mm for boards.
Thermal resistance Mean thermal resistance ≥ the design thermal resistance (as stated on the product).
Thermal resistivity ≥ 18.5 (m·K)/W
Surface burning characteristics For Type 1 products not intended for exterior of basement walls: Flame-spread classification shall not exceed 25. Smoke developed shall not exceed 50.
For Type 2 and 3 the test values shall be reported without reference to the acceptance criteria.
Smoulder resistance Applicable only to Type 1 products, not intended for exterior of Basement walls. Mean mass loss ≤ 2% and each specimen ≤ 3%.
Smoulder zone shall not reach specimen periphery.
Breaking load of exterior frame wall sheathing Not applicable to batts or rolls.
≥ 2.7 kg.
Applicable only to Type 2 boards for exterior frame wall sheathing.
Compressive resistance of draining insulation Not applicable to batts or rolls.
Applicable to draining insulation only. Compressive resistance for a 38 mm or thicker draining insulation shall be at least 7 kPa at 10% deformation and for thinner than 38 mm it shall be at least 10 kPa at 25% deformation.
Water vapour permeance Batts and Rolls: Not applicable for Type 1 products;
≥ 300 ng/(Pa·s·m2) for Type 2 products;
≤ 60 ng/(Pa·s·m2) for Type 3 products; and
Boards: Applicable to adhered membrane/insulation or to non-adhered membranes.
Corrosiveness Applicable to Type 1 batts and rolls.
Boards: corrosion ≤ control.
Fungi resistance Applicable to Type 1 batts and rolls.
Boards: growth ≤ comparative item.

Marking

The standard requires that packaging for the insulation be labelled or marked with the following information:

  • brand name and the name of the manufacturer or supplier;
  • identification of the manufacturing facility location;
  • type of insulation and its intended use;
  • net content of package in m2;
  • number of pieces per package;
  • design linear dimensions of the pieces in the package in mm;
  • design thickness in mm;
  • thermal resistance in (m2·K)/W to one decimal place;
  • on batts and rolls, the numerical thermal resistance value (or a simple code) displayed on the material at every 1.2 m length;
  • date of manufacture or shift code;
  • statement that the product complies with the standard; and
  • for preformed insulation without a membrane (Type 1 material), except for draining insulation, a cautionary statement:
    "CAUTION: Building, electrical, fire and other applicable codes shall be complied with. All heat-emitting devices, such as fuel-burning appliances, chimneys, pipes, ducts and vents to these appliances shall maintain a minimum clearance of 50 mm between these devices and the insulation. Recessed light fixtures, unless designed for the purpose, shall not be installed in insulated ceilings."

Note: Where applicable, the product shall carry additional information as stated below:

  • If the product is intended for application at thicknesses other than the design thickness, the thermal resistance and application for each intended secondary application shall be shown in similar print at a character height of at least ½ that of the design characters (with a minimum of 15 mm). The associated thickness of the secondary application shall also be shown. This secondary application, thermal resistance and thickness information shall be located on the same sides, excluding the ends, of the package as the design thermal resistance, application and thickness designations; and
  • Any necessary user safety information, unless a separate information sheet is provided.

Note:

Depending upon the jurisdiction, additional marking may be required by applicable acts and regulations.

National Building Code of Canada (NBC)

NBC References

The CAN/ULC-S702-09 standard is referenced in:

  1. NBC 2010, Division B, Table 5.10.1.1., Table 9.23.17.2.A. and Clause 9.25.2.2.(1)(d).

Evaluation Listing CCMC 09521-L: CertainTeed Fibre Glass Building Insulation, Golden Glow Residential Fibre Glass Insulation, UFA Residential Fiber Glass Insulation, Canadian Metal Building Insulation

Evaluation Issued:
1982-02-03
Re-evaluated:
2011-01-17
Revised:
Never
Re-evaluation due:
2013-07-13
Re-evaluation in progress
Yes

1. Evaluation

The product conforms to CAN/ULC-S702-09.

The design thermal resistance values are:

Design Thickness (mm)Design RSI (m2·K/W)
70 1.4
89 1.8Table footnote 1
89 2.1
89 2.4
152 3.5
140 3.8
140 4.2
191 4.9Table footnote 1
203 4.6Table footnote 2
216 4.9Table footnote 2
241 5.4
273 6.1
305 7.0
Notes to Table
Footnote 1

Only manufactured at the Redcliff, Alberta plant.

Return to table footnote 1 referrer

Footnote 2

Only manufactured at the Ottawa, Ontario plant.

Return to table footnote 2 referrer

2. Description

A Type 1, mineral fibre, thermal building insulation that is available in various sizes of friction-fit batts and rolls.

3. Standard and Regulatory Information

See the Preface and the standard for explanation.

Listing Holder

CertainTeed Insulation Canada, Inc.
3985 Belgreen Drive
OttawaON K1G 3N2

Telephone:
613-247-7116
Fax:
613-736-1150

Plant(s)

Ottawa, ON
Redcliff, AB

Disclaimer

This Listing is issued by the Canadian Construction Materials Centre, a program of NRC Construction at the National Research Council of Canada. The Listing must be read in the context of the entire CCMC Registry of Product Evaluations.

Readers must confirm that the Listing is current and has not been withdrawn or superseded by a later issue. Please refer to the CCMC web site, or contact the Canadian Construction Materials Centre, NRC Construction, National Research Council of Canada, 1200 Montreal Road, Ottawa, Ontario, K1A 0R6. Telephone (613) 993-6189. Fax (613) 952-0268.

NRC has evaluated the material, product, system or service described herein only for those characteristics stated herein. The information and opinions in this Listing are directed to those who have the appropriate degree of experience to use and apply its contents. This Listing is provided without representation, warranty, or guarantee of any kind, expressed, or implied, and the National Research Council of Canada (NRC) provides no endorsement for any evaluated material, product, system or service described herein. NRC accepts no responsibility whatsoever arising in any way from any and all use and reliance on the information contained in this Listing. NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.